Repo Dosen ULM

Analysis of C ondenser N-16000-2 U nit I PLTU I Central Kalimantan ( 2x60) MW

Show simple item record

dc.contributor.author Ghofur, Abdul
dc.contributor.author Arifin, Faishal
dc.contributor.author Subagyo, Rachmat
dc.contributor.author Mursadin, Aqli
dc.contributor.author Syarief, Akhmad
dc.contributor.author Amrullah, Apip
dc.date.accessioned 2023-04-10T00:17:50Z
dc.date.available 2023-04-10T00:17:50Z
dc.date.issued 2023
dc.identifier.uri https://repo-dosen.ulm.ac.id//handle/123456789/28088
dc.description.abstract This paper compares the performance of a condenser during the period between August and December 2018 to that during the commissioning period. It belongs to the Steam Power Plant (PLTU) I in Central Kalimantan. The comparisons are carried out in terms of the load, LMTD, temperature efficiency, capacity ratio, and effective heat transfer coefficient. The overall results suggest that time evidentlytakesitstollontheperformanceastheUeffdecreasedfrom1980W/m2K during the commissioning to 1319,4 W/m2K in December 2018. Fouling is the main reason for this. en_US
dc.language.iso en en_US
dc.publisher MIMSE-M-E 2022 en_US
dc.relation.ispartofseries AER 216;pp. 207-217
dc.subject Condenser · Ueff · Fouling en_US
dc.title Analysis of C ondenser N-16000-2 U nit I PLTU I Central Kalimantan ( 2x60) MW en_US
dc.type Article en_US


Files in this item

This item appears in the following Collection(s)

Show simple item record

Search DSpace


Browse

My Account